Orange County Health Care Agency /
Regulatory Health Services / Environmental Health
1241 East Dyer Road
Santa Ana, CA 92705
Telephone (714) 433 6090
I. INTRODUCTION
This Construction Guide is available
to any person intending to construct or remodel a Mobile food
facility for use in the County of Orange. The purpose of this guide
is to serve as a general overview of the requirements and may not be
all-inclusive. Mobile food facility (MFF) refers to any motorized
or non-motorized conveyance or portable food service unit upon which
prepackaged food or approved unpackaged food is sold or offered for
sale at retail. It does not include mobile support units (MSU's),
mobile food preparation units or stationary mobile food preparation
units. Please contact Environmental Health at the phone number
listed above if you require further information regarding your
particular plan.
A separate construction guide for
mobile support units, mobile food preparation units and stationary
mobile food preparation units is available upon request.
II. PLAN CHECK
FEES
A. A plan check fee must be paid
at the time of plan submittal. Current fee schedules are available
upon request
B. A remodel is any construction
or alteration to an existing food vehicle, which alters its
configuration or method of operation.
III. PLAN SUBMITTAL
A. Two sets of plans shall be
required for any new or remodeling MFF or support MFF prior to
construction or for MFFs that have been acquired by the operator in
the finished state. Plans may also be required for a change in menu
on an MFF that is presently permitted. MFFs that have been
previously permitted or construction reviewed may be accepted as
approved without plans as deemed appropriate by the present
jurisdiction processing the operating permit.
B. Complete and easily readable
plans shall be drawn to scale. Drawings shall show all 4 sides and
the top view of the MFF, with enclosure doors shown in open
position. The location and type of each of the following, if
applicable, shall be shown on the plan:
1. Potable water tanks (length
x width x depth indicated).
2. Potable water inlets (type
indicated).
3. Overflow lines.
4. Waste water tanks (length x
width x height indicated).
5. Waste tank drain valves.
6. Backflow prevention devices.
7. Water heaters (size in
gallons indicated).
8. Utensil and hand-wash sinks
(length x width x height indicated).
9. All associated plumbing.
10. Each piece of food service
equipment and its placement.
11. Specifications for the
equipment indicating manufacturer, make and model number shall be
indicated either separately or on the plan
12. Ice bins (length x width x
height indicated).
13. Finish schedule.
14. Food enclosure and
doors.
15. Gas and electrical lines.
16. All other component details
(such as utensils, tray inserts, insulations, counters, shelving,
storage areas, and food preparation areas, etc.).
C. Accompanying the Plans
1. A commissary agreement
letter, if available at that time, shall accompany the plans
(otherwise to be submitted prior to final issuance of a permit.).
2. A complete menu listing all
of he foods that you propose to prepare or sell from this unit.
3. Operational procedures for
food handling and the cleaning and sanitizing of food contact
surfaces and utensils.
4. For occupied MFF's,
certification for occupancy is required prior to permit approval.
IV.
CONSTRUCTION REQUIREMENTS
A. Food contact surface
materials of the MFF shall be durable, easily cleanable, smooth, and
shall not be constructed of unfinished wood.
B Construction joints shall be
tightly fitted and sealed with no gaps or voids. All sealant, solder
and weld joints located in the food contact areas shall be smooth,
and approved for food contact surfaces. Spaces around pipes,
conduits or hoses that extend through cabinets, floors or outer
walls shall be sealed to be smooth and easily cleanable.
C. All food-related equipment
and plumbing, including pumps, accumulators and filters, shall be
certified or classified for sanitation by an American National
Standards Institute (ANSI) accredited certification program, i.e.
NSF, ULS, ETL.
D. Water tanks and plumbing
shall be constructed of food grade material as approved by a
nationally recognized testing organization (such as ANSI) for
drinking water.
E. All food related fixtures,
tanks, equipment, plumbing, pumps and filters must meet standards
referenced in the plumbing code. Plumbing fixtures, pumps and
filters shall be installed according to the manufacturer’s
specifications. The local administrative authority or Health
Departments may require more stringent standards.
F. Equipment set apart from
adjacent equipment, or the clearance between the top of the counter
and the bottom of a piece of equipment with a rigid utility
connection shall provide a minimum gap of 4 inches of unobstructed
space to facilitate cleaning. Equipment that can be easily moved by
one person and has a flex connection need not comply with the above
requirement for 4-inch clear space.
G. Equipment shall be sealed to
the floor or raised 6 inches off of the floor by means of an easily
cleanable leg and foot (for Occupied MFF’s).
H. Lighting and Power Supply:
1. Light bulbs and tubes shall
be covered and completely enclosed with plastic safety shields or
the equivalent.
2. Light fixtures shall be
installed so as to not constitute a hazard to personnel or food
materials.
3. Adequate electrical power
shall be provided to all power accessories or appliances.
4. Electrical appliances shall
meet applicable Underwriter’s Laboratory (UL) standards.
5. Potable water tanks and
plumbing:
a. Interiors shall be smooth and
free of recesses and crevices and capable of draining completely.
b.
Tanks shall be adequately vented for flow.
c. Potable water tanks shall be
sufficient in volume to fulfill the required 5-gallon minimum for
hand washing and all other volume requirements for product
and utensil-washing water. For MFFs with blending vessels, an
additional minimum 10-gallon capacity for utensil washing and 15
gallon product water is recommended.
d. Water tank capacities may be
satisfied with only one or with multiple potable water tanks.
e. Potable water inlets shall be
protected from contamination and designed to preclude attachment to
a non-potable service connection, e.g. quick disconnect.
f. Potable water inlets shall
be located at least 1” above the overflow.
g. Overflow pipe
openings shall be protected from dirt, dust, insects and other
contamination.
|
V. MOBILE FOOD FACILITIES
LIMITED TO HANDLING OF PREPACKAGED FOODS AND WHOLE FISH
A. The display and sale of whole
aquatic invertebrates or bulk dispensing of non-potentially
hazardous beverages shall not require the hand/utensil sink required
in Section VI. A.
VI. MOBILE FOOD FACILITIES
HANDLING UNPACKAGED FOODS
A. The one compartment sink
shall be located on the operator side of the MFF and shall be
unobstructed and easily accessible. The sink can be either on the
countertop, or under counter, below a countertop cutaway extending
at least halfway from the edge of the sink to the faucet handles.
|
B. A permanent, single-use,
commercial towel dispenser shall be required.
C. A permanent hand-soap
dispenser shall be required.
D. The one compartment sink
shall be equipped with adequate plumbing fixtures that allow for
unobstructed utensil washing.
E. The one compartment sink
shall have hot and cold water through a mixing faucet capable of
delivering minimum one gallon/minute.
F. Water heaters shall be
at least ½ gallon capacity, and shall be capable of delivering water
at 120°F.
G. Cold running water at
101°F
or less shall be available.
H. Gas fired appliances:
1. Thermocouples shall have a
safety shut off device.
2. Propane tanks:
a. Propane tanks that are
enclosed within the MFF shall have at least two ventilation openings
on opposite sides at the cylinder valve level and at least one
ventilation opening required at the floor level. Each opening shall
be a minimum of 10 square inches, screened with a minimum 16 mesh
and shall vent to the exterior of the MFF.
b. The enclosure shall be free
of any source of ignition.
c. Propane tanks shall be
securely placed and should not be located on the bumper of a
trailer-mounted vehicle. The only appropriate placement outside the
body of the MFF is on the front (tongue) of the trailer.
d. Propane tanks shall have a
safety shut off valve.
e. Propane tanks shall require
the installation of a 3 lb. UL fire extinguisher.
3. Insulation is recommended
around the steam table, water heater and burner compartment to
prevent injury to the MFF operator or customer.
4. Gas fired appliances shall
meet applicable standards that are ANSI certified.
5. Certification shall be
indicated by a decal on the appliance.
I. Food enclosure(s): shall be
present and adequately sized for the intended operation of the MFF.
1. An enclosure shall fully
enclose and protect the food, contact surfaces, equipment and all
handling of ready-to-eat food. All food processing must remain
within the food enclosure, e.g. grinding and blending of coffee.
a. Doors shall be required to
allow complete enclosure during transport and non-operation of the
MFF and during operating hours whenever food preparation and service
is not occurring.
b. Doors shall be tight fitting
and vermin-proof (reference NSF Standard 59 for tight fitting).
c. Doors shall only open outward
and will not fold, flip or slide up and over the top portion of the
enclosure.
d. Folding side-by-side hinged
doors are acceptable.
e. Food enclosures shall be free
of electrical or plumbing lines with the exception of those lines
providing product supply water.
d. The food enclosure interior
shall have smooth cleanable surfaces.
e. Ice bins holding edible ice
shall be placed within an enclosure and will be designed for easy
access.
J. Food preparation counters:
Adequate counter space shall be provided for food preparation. All
food preparation counters shall be constructed of food grade
material.
K. Food enclosures shall be
vented to remove excess heat as necessary.
L. Food enclosure ventilation
shall be vermin proof.
M. Food Storage Compartments:
1. Food storage compartments
shall be large enough to accommodate expected food volumes.
2. Food storage compartments
shall be closed when not in use.
3. Food storage compartments for
sodas and hot dogs shall be in separate ice bins.
4. Food storage compartments for
dry goods and foods shall be in separate compartments.
5. Food storage compartments
shall not contain plumbing of any kind.
N. Mechanical refrigeration is
required for the storage of cream, milk or similar dairy products
and frozen ice cream bars.
O. All pressure cylinders shall
be securely fastened to a rigid structure.
P. Wastewater Tanks:
1 Wastewater tanks shall be of
sufficient capacity to hold 150% of the potable hand and utensil
wash water supply, 15% of product water and 33% of the total ice bin
volume.
2. All equipment, drain lines,
and drip trays shall drain to the waste tanks by an indirect
connection unless the waste tank is vented to prevent backflow.
3. Wastewater tanks may be
removable for easy disposal of waste.
4. Wastewater tanks shall have a
discharge valve located to facilitate complete draining of the tank.
5. Permanently installed steam
tables shall be fitted with a discharge valve and shall not drain to
the wastewater tank.
Q. Hand and utensil washing:
1. A one-compartment sink for
hand and utensil washing is required. The minimum size is 9x9x5
inches and large enough to accommodate the largest utensil.
2. The minimum potable water
tank size is five gallons. Additional potable water capacity is
required for product water (such as for making coffee) or other
activities other than hand and utensil washing.
VII. OCCUPIED MOBILE FOOD
FACILITIES
A. An occupied mobile food
facility means any wheeled conveyance that is occupied during normal
business operations and is used in conjunction with the service of a
commissary or other approved facility upon which prepackaged or
approved non-prepackaged food is sold or offered for sale at retail.
Occupied mobile food facility does not include a mobile food
preparation unit or a stationary mobile food preparation unit.
B. In addition to general
requirements for Mobile Food Facilities, the following shall apply
to Occupied Mobile Food Facilities.
C. Occupied Mobile Food
Facilities shall be certified for occupancy by the California
department of Housing (DOH). The DOH can be contacted at (909) 782
4420.
If the Mobile Food Facility has 110 volt electrical, plumbing, gas
mechanical generator or compressor, it must have an insignia issued
by the Department of Housing and Community Development.
D. Exterior requirements:
1. Entrance doors to food
preparation area and service openings shall be self-closing.
2. Service openings shall be no
more than 216 square inches and no less than 18 inches between
openings. Food service window requirements do not apply to vehicles
handling produce or prepackaged foods.
3. Service openings shall be
covered with solid material or screen. If screen is used it must be
at least 16 mesh per inch.
4. This section shall not apply
to MFFs that are limited to the handling of prepackaged food and
produce.
5. Compressor units that are not
an integral part of the mobile food facility shall be installed in
an area separate from the food prep and storage areas.
6. Propane tanks must be located
outside the MFF, and there can be no other attachments on the
exterior of the MFF (e.g. can opener).
C. Interior requirements:
1. Occupied Mobile Food
Facilities shall have a clear, unobstructed height over the
aisle-way portion of the unit of at least 74 inches from floor to
ceiling, and a minimum of 30 inches of unobstructed horizontal aisle
space.
2. Walls and ceilings shall be
constructed so surfaces are impervious, smooth and cleanable.
3. Floors shall be constructed
of approved materials.
4. The floor/wall juncture shall
be coved with a minimum 3/8-inch radius. The floor surface shall
extend up the wall at least four inches. (Vinyl rubber top-set base
is not acceptable material). This section shall not apply to mobile
food facilities that are limited to the handling of prepackaged
non-potentially hazardous food and produce.
5.
Unless
water flushing of floors is required. If water flushing of floors is
required, a food grade hose shall be installed and maintained in an
enclosed compartment. The food grade hose shall be of sufficient
length to clean the interior of the vehicle.
|